A hybrid inverter runs your solar panels, charges a battery and keeps selected circuits powered when the grid goes down. Growatt's SPH-HU-US series does all three in one split-phase 120/240V unit. The hard part is getting the three sizes right: the inverter (kW), the solar array (kW) and the battery (kWh). They're separate numbers, and each answers a different question. Here's how to work them out.
Three numbers, three questions
| Component | Measured in | The question it answers |
|---|---|---|
| Hybrid inverter | kW | How much can I run at the same time? |
| Solar array | kW (DC) | How much energy do I make over a year? |
| Battery | kWh | How long can I run on stored energy? |
A common mistake is treating them as one. A 10kW inverter doesn't mean 10 kWh of storage, and 15kW of panels doesn't mean you can power 15kW of loads at night.
Step 1: Size the inverter to your peak load
List what you want running at the same time during an outage, add up the watts, and allow for motor starts. Well pumps, central AC and refrigerators can briefly draw several times their running power.
- Essentials (fridge, freezer, lights, internet, furnace fan, well pump): typically 3–6 kW at peak.
- Most of the house, including a mini-split or window AC and a microwave: 8–10 kW.
- Whole home with central AC, electric range or EV charging: 12–18 kW or more, or two inverters in parallel.
The Growatt SPH-HU-US range
All four models are 48V (low-voltage) battery inverters with split-phase 120/240V output, according to our product pages and Growatt's datasheet. Prices as of November 2026:
| Model | Rated AC output | Max recommended PV | Max battery current | Price |
|---|---|---|---|---|
| SPH 10000TL-HU-US | 10,000 W | 15,000 W | 200 A | $2,999.99 |
| SPH 11500TL-HU-US | 11,500 W | 23,000 W | 240 A | $3,500.00 |
| SPH 15000TL-HU-US | 15,000 W | 30,000 W | 312.5 A | $4,250.00 |
| SPH 18000TL-HU-US | 18,000 W | 36,000 W | 334 A | $4,450.00 |
The SPH 10000 has three MPPT inputs, a 10 ms backup transfer and a 10-year Growatt warranty, and it supports new DC-coupled installs and AC-coupled retrofits onto an existing grid-tie system. The larger models add more PV capacity, a 200A grid passthrough and up to 30kW of generator input. Up to six units can run in parallel. Compare them all in Residential Hybrid Solar Inverters, or see every Growatt inverter and battery we stock.
Step 2: Size the solar array to your annual use
Find your annual kWh on your utility bills, then divide by how much each kW of panels makes where you live. NREL's free PVWatts calculator gives that figure for your address, roof tilt and direction.
Array size (kW) ≈ annual kWh you want to offset ÷ PVWatts kWh per kW per year
Hybrid inverters let you oversize the array relative to the inverter. The SPH 10000 accepts up to 15kW of recommended PV and the SPH 18000 up to 36kW, which helps in winter and on east/west roofs.
Step 3: Size the battery to your backup goal
Battery kWh ≈ the daily energy of the loads you'll back up × the hours you want to cover ÷ 24. With solar recharging the battery each day, you need less than for a battery-only system.
Two 48V batteries work with the SPH range (prices as of November 2026):
- Growatt ALP LV-US 5kWh 48V LiFePO4 battery — $1,699.99. 5.12 kWh nominal and 4.6 kWh usable per module. It communicates with the SPH over CAN and stacks up to 40.96 kWh.
- GSL Energy 14.34kWh 48V LiFePO4 battery — $2,899.99. 13.623 kWh usable at 95% depth of discharge, in an IP65 outdoor-rated enclosure.
Growatt's APX battery is a high-voltage battery for the MIN XH-US series and does not work with the SPH.
Worked example
A home uses 12,000 kWh a year and wants to keep the fridge, freezer, lights, internet, furnace fan, well pump and a mini-split running through outages.
- Inverter: backed-up loads peak around 7 kW with a well pump start. The SPH 10000 (10 kW) covers that with headroom.
- Solar: if PVWatts shows about 1,000 kWh per kW per year for this roof, 12,000 ÷ 1,000 = 12 kW. That's within the SPH 10000's 15kW PV limit.
- Battery: those loads use about 12 kWh a day. To cover a night and the next morning with solar recharging during the day, about 13–18 kWh usable is a good target: one GSL 14.34kWh, or four ALP modules (18.4 kWh usable).
That's very close to our 10kW Hybrid Solar Kit: an SPH 10000TL-HU-US, 27 × 450W JA Solar bifacial panels (12.15kW) with Tigo rapid shutdown, and either a GSL 14.34kWh battery ($11,499.99) or four Growatt ALP batteries, 20.48 kWh nominal ($13,999.99), as of November 2026.
Complete Growatt hybrid kits
If you'd rather start from a matched system, our Hybrid Solar System collection includes (prices as of November 2026):
- 6kW Hybrid Solar System — $9,699.99. A Growatt MIN 6000TL-XH-US, 7.2kW of panels, a 10kWh Growatt APX high-voltage battery and an automatic transfer switch for partial-home backup.
- 10kW Hybrid Solar Kit — from $11,499.99, as above.
- Growatt 18kW Hybrid Solar Kit — $25,950.00, with 31.59kW of ZNShine panels and 43.02kWh of GSL storage for whole-home backup.
- 20kW Hybrid Solar System — from $24,999.98, with 24.57kW of PV and a choice of GSL or Growatt ALP storage.
Low-voltage or high-voltage?
Growatt makes both. The SPH-HU-US series uses 48V batteries, which are widely available, modular and easy to expand one module at a time. The MIN XH-US series uses the APX high-voltage battery, which comes as a matched system with the inverter. If you want to mix battery sizes over time or reuse a 48V bank, the SPH is the more flexible choice.
FAQ
What size Growatt hybrid inverter do I need?
Add up the loads you want to run at the same time during an outage, including motor starts. Most homes backing up essentials plus a mini-split land on the SPH 10000; whole-home backup with central AC usually needs the 15kW or 18kW model, or two units in parallel.
Can I add a Growatt hybrid inverter to my existing solar?
Yes. The SPH supports AC-coupled retrofits, so you can add battery backup to an existing grid-tie system.
Can I charge the battery from a generator?
Yes. The SPH series supports generator charging, with up to 30kW of generator input listed on the datasheet.
Is there a federal tax credit for solar and batteries?
The IRS says the residential clean energy credit is not available for expenditures made after December 31, 2025 (IRS, checked November 2026). Some states and utilities still offer rebates, so check what applies where you live.
Do I need an electrician and utility approval?
Yes. Installation must follow the manual, the NEC and local code, be done by a licensed electrician, and be approved by your utility when the system is grid-connected.
Send us your utility bills and the loads you want to back up, and we'll size a Growatt system for you at no cost.